Post Buy Requirement
EM
Sharjah, United Arab Emirates
Add Review

Relays & Contactors #2956181

Numerical Overcurrent & Earth Protection Relay Type

MJT 314over current relay combines the power and flexibility of microprocessor technology with decades of experience in the field of protection. A wide range of protection elements and characteristics are supplemented by advance features such as metering, fault recorder and communication. MJT 314 offers inverse time and definite time over current protection for phase fault and earth fault with communication.

Application

  • Distribution Feeders
  • Transmission lines
  • AC machines
  • Capacitor banks
  • Transformers
Standard Features
IDMTL / DTL phase fault over current stage (50/51) IDMTL / DTL earth fault over current stage (50N/51N)
Readable human machine interface with backlit LCD display Digital input for group changeover application
Two group settings Storage of five fault records
Internal realtime clock Suitable for flashing faults
Both 1 A and 5 A ratings in same relay Wide range of current settings
Suitable for wide range of auxiliary supply Non volatile memory for trip indication
Low AC and DC burden Self monitoring facility
View Complete Details

Numerical Check Synchronizing Protection Relay Type

ARGUS 7is a combined check and system synchronising relay which can automatically select check or system synchronise from measurements of the relative phase angles between line and bus voltages. The relay will prevent closure of the circuit breaker if either the phase angle, slip frequency or the voltage magnitude of the incoming and running voltages fall outside prescribed limits.
If the parameters are within the limits the relay will issue an output which can be used to close the circuit breaker directly or in conjunction with an autoreclose scheme. Both the check and system synchronise functions have independent settings and blocking features. The relay includes split system detection with a variable time delay, which can be used for blocking purposes within delayed autoreclose schemes.
Synchronising bypass logic is provided to connect a dead line or bus to a live line or bus. For manual synchronising the relay includes a circuit breaker close guard feature which is used to prevent the control switch being held closed during a synchronising operation. This feature is implemented using internal logic and removes the need for an external relay.

Application

  • Check-synchronizing
  • System-synchronizing
Standard Features
Check synchronizing (25) and system synchronizing Under voltage blocking (27)
Differential blocking 4 programmable digital inputs and 7 programmable outputs
Configurable dead bus and/or dead line charge Adjustable slip frequency, phase angle and time delay
Integrated manual close guard feature Independent check synchronizing and system synchronizing settings
View Complete Details

Multi-function Bus Protection Relay Type

B-PRO 4000relay provides bus and substation differential protection (low impedance) with CT saturation security, integrated breaker failure, overcurrent protection and SCADA control in a fully integrated protective relay solution. The B-PRO 4000 relay also provides control, automation, metering, monitoring, high capacity for DFR quality fault oscillography, dynamic swing recording and sequence of events logging. The B-PRO 4000 relay is suitable for simple bus applications with up to 6 feeders and 2 differential zones with breaker failure, or 4 feeders and 1 transformer, including separate full transformer differential protection.

Application

  • Bus and substation differential protection (low-impedance)
  • Re-configurable simple bus application up to 6 feeders and 2 differential zones
  • Separate Transformer differential protection
  • 6 sets of CT inputs for differential protection (18 currents) using percentage slope characteristic for security on external faults
  • Low impedance design allows different CT ratios for each of the 6 inputs
  • Backup overcurrent and breaker failure for each input current
  • User defined directional control of overcurrent functions for networked lines
  • 3 phase voltage inputs to apply over/under voltage and frequency functions
  • 1 or 2 separate differential zones - bus and transformer or Bus 1 and Bus 2 for multiple buses
  • ProLogic - control logic statements
  • 30 virtual inputs for local or remote control applications

Standard Features
Multiple zones of protection-transformer, bus and dual bus zones
IEC 61850 communication via optical ports
Protection functions include IEE devices 87B, 27, 59, 60, 81, 87T, 50LS, 50BF, 50/51/67, 50N/51N/67, 46/50/51/67
IRIG-B time stamping and sample synchronization
96 samples/cycle falut recording, swing recording and event logging(1ms)
Enhanced DNP3 SCADA communication protocol including point lists, class support and multiple master station support
View Complete Details

Sub-Harmonic Protection Relay Type

S-PRO 4000is a digital, microprocessor-based sub-harmonic protection system that provides comprehensive sub-harmonic protection for transmission lines at any voltage level, particularly those with serial compensation and interconnected with wind farms. Use the S-PRO Sub-Harmonic Protection Relay for monitoring and protection of uncontrolled sub-harmonics, ensuring a reliable operation of the power grid.
Undamped sub-harmonic current oscillations created by series capacitors interacting with the wind system can cause serious damage to wind turbine controllers and also to conventional generators. The wind turbine's own mechanical system interactions (tower-to-blade) can also generate sub-harmonics, which are detrimental to induction generators, transformers, and may cause resonance at the point of common coupling in the electrical grid.
The S-PRO 4000 relay detects these sub harmonic oscillations and allows the utility to monitor and protect the power system by isolating the healthy grid from sub-harmonic generation sources.

Protect against sustained sub-harmonics in wind farm operations

Undamped sub-harmonic current oscillations created by series capacitors interacting with the wind system can cause serious damage to wind turbine controllers and also to conventional generators. The wind turbine's own mechanical system interactions (tower-to-blade) can also generate sub-harmonics, which are detrimental to induction generators, transformers, and may cause resonance at the point of common coupling in the electrical grid.
The S-PRO 4000 relay detects these sub harmonic oscillations and allows the utility to monitor and protect the power system by isolating the healthy grid from sub-harmonic generation sources.

Features and Benefits

  • Built on a contemporary new substation hardened hardware platform and powered by a state-of-the-art processor
  • Protects the grid from sub harmonic oscillations at the point-of-common-coupling every 1 second, with additional user-configurable delays
  • Provides real time processing of voltage and current signals, comprehensive sub-harmonic protection, with sub-harmonic monitoring for each frequency in the range from 5 Hz to 40 Hz
  • Flexible Communications
    • State-of-the-art communications (2 rear ports, 100BASE-TX RJ-45 or 100BASE-FX 1300 nm multimode optical with ST style connector to accommodate the industrys latest network-based communications)
    • Ethernet ports with 2 unique MAC addresses that easily accommodate network access security needs
    • Front panel USB and 100BASE-TX RJ-45 Ethernet port interfaces (readily accommodate modern standard laptops)
  • Reduced Cost
    • Product setting time 240 x 128 LCD graphical user interface provides convenient means to check/change specific settings and parameters
  • Improved Overall Response Time
    • Expedited response to systems events (11 generic front panel LEDs can be mapped to internal elements) allowing operators to quickly identify the cause of system events

Easy to Use

  • Flexible programmable logic for building customized schemes with ProLogic statements 24 control logic statements (total of 192 statements)
  • User-friendly, Windows-based relay setting and record analysis software
  • Enhanced DNP3.0 Level 2 SCADA communication protocol including user-selectable point lists, class support and multiple master station support
  • Exceptional fault recording capabilities with 96 s/cycle, all channels with events (best combination of waveform accuracy and file size)

Application

  • Sub-harmonic protection for transmission lines, particularly those with serial compensation and interconnected with wind farms
  • Single and multi breaker applications
Standard Features
Built on a contemporary new substation hardened hardware platform and powered by a state-of-the-art processor Protects the grid from sub harmonic oscillations at the point-of-common-coupling every 1 second
Fundamental frequency protection functions IEEE devices 27, 50LS, 59 Real-time processing of voltage and current signals
8 setting groups for many operating conditions
View Complete Details

Motor Protection Relay Type

RHO 3is used for protection and management of medium and large motors and driven equipmentIt is Ideally suited for pumps, conveyors, compressors, fans etc.

Standard Features
Thermal overload protection (49) Circuit breaker failure protection (50 BF)
Communication protocol compatible with IEC 60870-5-103 or MODBUS RTU Thermal overload protection (49)
CT Supervision Earth fault Protection (50N)
Fiber-Optic/ RS485 Communication port LCD Display
Limitation of number of starts Fiber-Optic/ RS485 Communication port
Optional 8 thermistor or Resistance Temperature Detector (RTD) Inputs Phase unbalance protection (46)
Restart inhibit protection Short Circuit Protection (50)
Stall and Locked Rotor Protection (48) Upto 9 programmable digital inputs & upto 7 programmable output contacts
Undercurrent detection (37)
View Complete Details

Numerical Voltage Frequency Protection Relay Type

ARGUS 8range of numerical voltage and frequency relays have the power and flexibility of microprocessor technology, giving a wide range of settings which are supplemented by advanced features such as metering, data storage and Fibre-Optic communications. Supervisory and self-monitoring features give added confidence to the user as well as reduced maintenance and down time. A menu-based interface gives user friendly access to relay settings, meters and operational data

Application

  • Capacitor banks
  • Ungrounded/ High impedance earthed systems
  • AC generators
  • Transmission lines
  • Distribution feeders
Standard Features
Over voltage (59) and under voltage (27) Neutral voltage displacement
Negative sequence over voltage (47) Over frequency (81O)
Under frequency (81U) Trip circuit supervision (95)
2 pole and 3 pole versions 7 programmable output relays
4 programmable digital inputs (2 pole) Up to 9 programmable digital inputs (3 pole)
View Complete Details

Feeder Protection Relay Type

F-PRO 2000is a family of Multifunction Numerical relays, meant for protection of Transmission and Distribution equipment. Each relay in the family is loaded with a set of functions which can suit the requirements in a variety of power automa t ion applications. The products in the family are configured with a set of current and/or voltage operated protections, metering and data communication functions. For analysis, the products includes Fault logs, Disturbance recording and 1000 Sequence of events with 1ms time stamp resolution. As relay is draw out in construction it can be easily replaced in the eventuality of failure.

Application

F-PRO 2000 provides current and/or voltage protection for Lines, Transformers, Generators, Motors, Busbars, Reactors, Capacitors etc. Rear Communication capability allows integration into a Substation Automation or Monitoring System/SCADA.

Functions
F-PRO 2000 series of relays offer various current and over voltage protections packaged into simple to use configurations.

  • Dir./Non-Dir. Over Current Protection (67/50/51)
  • Non-Dir. Measured Ground Fault Protection (50G/51G)
  • Dir / Non - Dir. Derived Ground Fault Protection(67N/50N/51N)
  • Negative Sequence Over Current Protection(46/50/51)
  • Restricted/Sensitive (Non Dir.)/Standby Ground Fault Protection(64REF/50SE F/51SEF)
  • Broken Conductor Detection (46BC)
  • Negative Phase sequence Over Voltage Protection (47)
  • Thermal Over Load Protection (49)
  • Circuit Breaker Failure Protection (50BF)
  • High Impedance Differential protection (87/50)
  • Phase Under/Over Voltage Protection (27/59)
  • Derived Residual Over Voltage Protection (59N)
  • Measured Residual Over Voltage Protection (59G)
  • Overflux Protection (24)
  • Under/Over Frequency Protection (81U/81O)
  • Rate of Change of Frequency Protection (81R)
  • Four Shot Auto Reclose Function (79)
  • Synchro Check/Energizing Check (25/27/59)
  • Current Transformer Supervision (60CTS)
  • Voltage Transformer Supervision (60VTS)
  • Trip Circuit Supervision (74TCS)
  • CB Monitoring (I t)
  • Transformer Inrush Detection & Restraint (81HBL2)
View Complete Details

Feeder Protection Relay

  • Theory Solid State Relay
  • Protect Feature Feeder Protection
  • Place of Origin India
  • Lead Time 8 weeks
  • Usage Protective
View Complete Details

Numerical Biased Differential Protection Relay Type

MIB 202works on the current differential principle and takes the current inputs from both the ends of two winding power transformer and auto transformer. It provides stability against magnetic inrush conditions. Load/through fault stability is achieved through bias setting provided in the relay. It operates only for internal faults

Application

  • Two winding power transformers
  • Auto transformers
  • Biased differential protection for generators
Standard Features
Numerical, true RMS measurement Both 1A & 5A CT inputs in one relay
Both DC & AC auxiliary supply available Drawout modular case (150X151mm cutout )
Compact design Non-volatile memory for trip indication
Self-monitoring facility 7 segment LED display
Status indication LEDs Sealable front cover to prevent unauthorised access
Biased differential (87) Instantaneous differential highset
Integrated current amplitude multiplier & vector group compensation No interposing C.Ts required
3-slope adjustable bias setting Immune to magnetic inrush
5 output contacts
View Complete Details

Inverse Definite Minimum Time Lag Overcurrent Protection Relay

2TJMRelay is available in three versions viz. 2TJM 10, 11 and 12. These are disc-operated relays, and provide IDMT, single/three pole, overcurrent protection, with/without highset and with/without directional and phase fault protection. The 2TJM relays are completely drawout, and have 2NO contacts for external tripping purposes.

2TJM10:The relay comprises a die-cast frame, which carries all the sub-assemblies of induction disc, electro-magnetic system, operating coil, plug bridge and the contact assembly. Instantaneous highset and directional elements can be provided.
The electro-magnetic system comprises primary and secondary magnets arranged with four air gaps each contributing to the driving torque. The primary coil energises the primary magnet and a secondary winding which in turn energises the secondary magnet. Tappings on the primary coil permit various fault settings to be made via a plug-bridge. The plug-bridge automatically selects the highest setting when the setting-plug is withdrawn.
Two normally open contacts are provided of the bridging type, the operating arm being driven by a cam track at the hub of the induction disc. This gives considerable mechanical advantage and ensures high contact pressures, even at low operating current levels, making the contacts suitable for direct tripping.
Relay operating time is determined by the starting position of the induction disc, this is set by the time multiplier dial calibrated from 0.1 to 1.0, there is also a ^T^ mark, before the 0.1 setting, in this position the contacts are held closed, locked out. Settings are applied in ampere.

2TJM11:The type 2TJM11 relay is basically similar to the type 2TJM10, the exception being the addition of a miniature instantaneous high-set overcurrent element (type MCAA) which is fitted to the movement frame and has its operating coil connected in series with the relay primary coil. The element is of the attracted armature type and primarily designed for use with I.D.M.T.L. relays. The overcurrent setting is continuously variable by means of the calibrated cam. This element may be ^locked out^ by advancing the setting adjuster to its extremity, i.e. past the highest fault setting. The flag indicator shows on operation and is hand reset by a push fitted in the relay cover.

2TJM12:This relay comprises the I.D.M.T.L. element previously described and a directional element type ^ES^. The elements are vertically mounted on a mild steel back-plate with the directional element in the upper position; the composite relay is then housed in a 11/2 pole vertical case.
The directional element operates on the induction wattmeter principle and consists essentially of an aluminium sector mounted on a vertical spindle and arranged to rotate in the air gap between the magnetic fields derived from the line current and voltage transformers. The electro magnetic system with the three coils which provide loss of voltage compensation and hence reliable operation should the line voltage be reduced, under fault conditions, to values as low as 2% of nominal.
Under healthy system conditions or under fault conditions where the current flow is in the normal direction eddy currents induced in the sector produce a torque, the direction of which restrains relay operation. Should current reversal occur, then the direction of the torque reverses causing the moving system to rotate and thus close the contacts, the latter being so connected that they complete the I.D.M.T.L. element operating coil circuit.
The maximum torque exerted on the movement occurs when the voltage and current in the coils are in phase. However, as the system power factor may be considerably removed from unity under fault conditions, depending on both the nature of the fault and system conditions, the element can be supplied with a phase-angle introduced by fault conditions. This is achieved by employing a suitable shading ring, the requisite value of resistance and the appropriate connection.

Phase-Fault Relays:45 degree Lead Power Factor Characteristic: Relays supplied with the 45 degree lead power factor characteristic utilise the 90 degree connection, i.e.relays monitoring A-phase current are polarised by B-C voltage, thus the relay develops maximum torque with a 45 degree lagging fault current.

Earth-Fault Relays:Earth-fault relays are normally supplied with 12 and half degree lagging power factor characteristic. The current coil is connected in the residual circuit of the line current transformers and the voltage coil in the open delta tertiary winding of the line voltage transformer, the voltage coil being suitable for 190V and 63.5V on resistance and solidly earthed systems respectively.
Directional earth fault relays with a 45 lagging power factor characteristics are used in highly inductive earthing systems. The characteristic is achieved in the relay with a RC circuit in the ES element.

Standard Features
No Standing drain on substation battery supplies Easy to test and maintain
Extremely long service life Designed to comply with IEC 60255 specializations
View Complete Details
Tell Us What are you looking for? Will call you back

Contact Us

  • Mr. Abhijit Dasgupta (ERL Marketing International)
  • No.1K – 08/02, PO Box 50669,Hamriyah Free Zone, Sharjah – UAE.
  • Share us via

( ! ) Warning: Cannot modify header information - headers already sent by (output started at /htmlcachedir2/dynamic-html-pages/eitempfilen/uae/company/erl-marketing-international/relays-contactors.htm:44) in /home/sgupta/exportersindia.com/htdocs/script-files/company-page/index.php on line 59
Call Stack
#TimeMemoryFunctionLocation
10.0006457896{main}( ).../index.php:0
20.01752061168include_once( '/home/sgupta/exportersindia.com/htdocs/script-files/country-vanity/country_index_page_common_script.php' ).../index.php:309
30.02592775432include_once( '/home/sgupta/exportersindia.com/htdocs/script-files/company-page/index.php' ).../country_index_page_common_script.php:282
40.03183715800header ( ).../index.php:59
ExportersIndia: 404 Error Found
404Oops! It seems this page is not available

We connect Buyers and Sellers

Tell us What you Need

Trending Categories

Find Suppliers by Region


View All Categories

Find Suppliers by Country

Waiting for permission
To search by voice, go to your browser settings and allow access to microphone

Allow microphone access to search with voice