The DALI addressable hub can be used in isolation to provide simple control to a localised application such as a classroom or office area. It has the added flexibility of being able to control multiple rooms up to the maximum addresses as detailed below.
Low profile housing, perimeter mounted connector for mounting in limited void space
Integrated mounting detail for surface, rod or trunking fixing
Output connections
4 x 6 pole lighting outputs rated at 6A (16A total maximum load)
Injection moulded flame retardant housing with mains entrycover and cable retainer
Integrated DALI power supply
System Guidelines
Up to 63 addresses per hub (each ballast, detector or switchconstitutes 1 address)
Maximum 300m cable run and 250mA power consumption(typical 2mA per ballast)
Up to 6A load on each of 4 socket outlets (16A totalmaximum load)
Simple Wiring
Enhanced connectivity with CFL wiring components
Switches and detectors can also be connected with CFL cables
Software Configuration
Post installation software interface can be used to definedimming zones for daylight harvesting or switching zones
Scene Setting
Touch button panels can be programmed to control a variety ofdifferent scenes by individually addressing each luminaire within the space
Simple corridor linkage can be programmed so the luminairesstay on at a defined level whilst adjoining areas are occupied
Multiple lighting levels can be selected from the switch panel
Switching in X direction and daylight control in Y direction ispossible